Open air events

Section 1: Fire Risks and Preventative Measures
The primary strategy for fire prevention is the systematic separation of flammable materials from ignition sources.
Housekeeping and Storage Effective housekeeping reduces the likelihood of fire and prevents escape routes from becoming obstructed. Combustible waste should be kept in suitable containers and removed regularly. Skips and wheeled bins must be secured in compounds to prevent arsonists from moving them against structures; skips should be at least 6 metres away from any structure.
Storage management is critical. Retail areas are often well-maintained, but storage areas can become neglected. To reduce risk:
Store excess materials in dedicated, monitored areas away from the public.
Avoid vertical stacking of materials like rolls of cardboard, which allows fire to spread rapidly upwards; horizontal stacking is preferred.
Keep outdoor storage, pallets, and vehicles away from temporary buildings, stages, and fire exits.
Clear waste and dry vegetation to prevent the spread of outdoor fires to structures.
Dangerous Substances Highly flammable liquids (e.g., petrol for generators) present a severe risk as their vapours can travel long distances to ignition sources. Only a daily supply—up to 50 litres—should be kept in a fire-resisting cabinet or bin; larger amounts require a dedicated store.
LPG (Liquefied Petroleum Gas) must be stored upright in secure, well-ventilated locations away from ignition sources and corrosive materials. All gas piping should be made of rigid material wherever practicable. Fireworks and pyrotechnics require rigorous pre-planning and must be stored in secure, ventilated, fire-resistant enclosures. A clear policy should prohibit the public from bringing flares or fireworks into the venue.
Equipment and Machinery Machinery must be maintained by competent persons to prevent friction, overheating, or electrical faults. Key measures include:
Heating: Fixed convector or fan heaters are preferred; portable fuel-burning heaters should only be used in public areas in exceptional circumstances if supported by the FRA.
Cooking Processes: Siting cooking near combustibles should be avoided. Ductwork requires regular cleaning to prevent grease fires, and deep fat fryers should have automatic temperature cut-offs and fire suppression systems.
Electrical Safety: Faulty equipment is a leading cause of accidental fires. Portable equipment should undergo Portable Appliance Testing (PAT), and fixed installations must be inspected by competent engineers.
Restricting Fire Spread The materials used in structures significantly affect fire growth.
Tents and Marquees: All fabric should meet fire performance standards (e.g., BS 7837). Flame-retardant treatments may need periodic renewal if the fabric is exposed to weathering.
Air-Supported and Pneumatic Structures: These are vulnerable to collapse if fire damages the membrane at a high level, reducing internal pressure. Reliability of air supply systems and flame-retarded materials are essential.
Insulated Core Panels: Damage to the metal skin of these panels must be repaired immediately to prevent fire from exposing the combustible core.
Arson and Special Needs Arson prevention involves well-lit perimeters, secure storage for flammables, and regular rubbish removal. Owners must also anticipate the needs of disabled persons, providing ramps for wheelchair users and developing Personal Emergency Evacuation Plans (PEEPs) to ensure everyone can leave safely.
Section 2: Fire Detection and Warning Systems
The purpose of these systems is to alert occupants quickly enough to allow safe evacuation before routes are compromised.
System Types In small, simple events, a shout of "fire" or a manual gong or air horn may suffice. Larger or complex venues require:
Electrical Warning Systems: These include manual call points (break-glass boxes) positioned at exits so that no one travels more than 45 metres to reach one.
Public Address (PA) Systems: These are often the most effective way to provide explicit instructions and direct evacuation at large sites.
Automatic Fire Detection (AFD): Necessary for lone workers, unoccupied areas (storerooms), or as a compensatory feature for extended travel distances.
Testing and Maintenance A responsible person must supervise the system. MCPs should be tested weekly, and professional servicing by a competent person is required every six months. Electrical systems must have a backup power supply capable of operating for 24 hours and sounding the alarm for 30 minutes.
Section 3: Firefighting Equipment and Facilities
Portable Extinguishers Extinguishers tackle small fires in their early stages. For standard (Class A) risks like wood or paper, provide one water-based extinguisher for every 200m² of floor space in enclosures, with a minimum of two per floor.
Siting: They should be on escape routes near exits, with a maximum travel distance of 30 metres to reach one.
Types: Water (red), Foam (cream), CO2 (black), and Class F (canary yellow) for deep fat fryers.
Maintenance: Monthly visual checks by staff and annual professional maintenance are required.
Fixed Systems and Fire Points Large sites should provide fire points—highly visible locations containing equipment like standpipes with hose reels, or water tanks and buckets.
Facilities for Firefighters Owners must ensure fire engines can approach within a reasonable distance.
Fire Lanes: Must have a minimum road width of 3.7m, gate width of 3.1m, and be capable of carrying a 12.5 tonne vehicle.
Access: Fire lanes should be kept clear of parked cars and be within 50m of any part of the event.
Information: Provide the fire service with site plans showing access routes, hydrants, and high-risk areas upon arrival.
Section 4: Escape Routes and Strategies
The goal is for all occupants to reach a place of total safety